NOx Tests on Hospital Boiler

A source test was performed on a boiler at St. Mary Hospital in Long Beach, California using 100% biodiesel treated with the RxP technology.  The tests were performed by World Environmental, a certified testing laboratory approved by the South Coast Air Quality Management District in California.  The purpose of these tests was to determine if 100% biodiesel could be used in lieu of natural gas.  See newspaper article.

2.0 SUMMARY OF RESULTS

Facility: St. Mary’s Medical Center

Date Tested: June 12, 2001

Unit: Boiler #3

Project #: WER695

A. Boiler Run #1 (Low Fire)

Parameter

ppm

(drift corr)

ppm

@ 3% O2

Allowable Emissions

@3% O2

Soy Bean Oil

@5.98% O2

NOx

CO

 

 

24.89

103.80

 

 

24.14

29.85

 

 

40 ppm

400 ppm

 

B. Boiler Run #2 (Mid Fire)

Parameter

ppm

(drift corr)

ppm

@ 3% O2

Allowable Emissions

@3% O2

Soy Bean Oil

@5.24% O2

NOx

CO

 

 

23.32

207.37

 

 

26.65

236.97

 

 

40 ppm

400 ppm

 

C. Boiler Run #3 (High Fire)

Parameter

ppm

(drift corr)

ppm

@ 3% O2

Allowable Emissions

@3% O2

Soy Bean Oil

@5.50% O2

NOx

CO

 

 

28.13

39.82

 

 

32.68

46.25

 

 

40 ppm

400 ppm